111 Progress Ave. New Castle, PA 16101 Tel: (724)658-3551 Tel/Toll Free: (800) 245-4455 Fax: (724) 652-0682 Email: airdoors@berner.com Website: http://www.berner.com http://www.berner.com [Click Here] for additional information. Berner International Corporation manufactures a complete line of industrial and commercial/retail air doors / air curtains. Our air curtains are available heated or unheated and provide fly/insect control, environmental separation, refrigeration loss, and fume/odor control. Custom engineered air curtains are available for special applications. Our product line also includes strip doors, air entrance systems, and our 'Posi-Flow' fabric ducts. No one else offers Berner's standards of quality, performance, and dependability, not to mention our service. At exterior openings, air doors can resist winds up to 8 MPH and are generally mounted inside building to recirculate warm air, which has risen towards ceiling. Air doors may not be fully effective where negative air pressure exists on one side of door; contact Berner for additional information. A selection guide is available at www.berner.com to suggest models appropriate for typical applications. For additional information or the name of Berner representative in your area, call Berner International Corporation at 800-245-4455 in U.S. or 800-242-4455 in Canada, or visit www.berner.com. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| PART 1 | GENERAL | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1.1 | SECTION INCLUDES | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Air doors. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1.2 | RELATED SECTIONS | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Section 06100 - Rough Carpentry. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Section 05410 - Load-Bearing Metal Studs | |||||||||||||||||||||||||||||||||||||||||||||||||
| C. | Section 08110 - Steel Doors and Frames. | |||||||||||||||||||||||||||||||||||||||||||||||||
| D. | Section 08400 - Entrances and Storefronts. | |||||||||||||||||||||||||||||||||||||||||||||||||
| E. | Section 08500 - Windows. | |||||||||||||||||||||||||||||||||||||||||||||||||
| F. | Section 08580 - Pass Windows. | |||||||||||||||||||||||||||||||||||||||||||||||||
| G. | Sections of Divisions 15 and 16 affecting, or affected by, construction activities of this section. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1.3 | REFERENCES | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | AMCA 220 - Air Curtain Units. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | ARI 410 - Forced-Circulation Air-Cooling and Air-Heating Coils. | |||||||||||||||||||||||||||||||||||||||||||||||||
| C. | NEMA 250 - Enclosures for Electrical Equipment. | |||||||||||||||||||||||||||||||||||||||||||||||||
| D. | UL 507 - Electric Fans. | |||||||||||||||||||||||||||||||||||||||||||||||||
| E. | UL 508 - Industrial Control Panels. | |||||||||||||||||||||||||||||||||||||||||||||||||
| F. | ANSI/NSF 37 - Air Curtains for Entranceways in Food Establishments. | |||||||||||||||||||||||||||||||||||||||||||||||||
| G. | NFPA 54 - National Fuel Gas Code. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1.4 | SUBMITTALS | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Submit under provisions of Section 01300. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Product Data : Manufacturer's data sheets on each product to be used, including: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Preparation instructions and recommendations. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Storage and handling requirements and recommendations. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Installation methods. | |||||||||||||||||||||||||||||||||||||||||||||||||
| C. | Shop Drawings: Indicate installation and connection details. | |||||||||||||||||||||||||||||||||||||||||||||||||
| D. | Certificates: Indicate compliance to Regulatory Requirements and Performance Requirements. | |||||||||||||||||||||||||||||||||||||||||||||||||
| E. | Closeout Submittals: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Operation and maintenance data: Manufacturer's printed instructions for operating and maintaining air curtain components. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Warranty documents: Issued and executed by manufacturer. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1.5 | QUALITY ASSURANCE | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Manufacturer Qualifications: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Products in satisfactory use in similar service for not less than five years. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Manufactured and assembled in the United States of America. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Regulatory Requirements: Product compliance with the following regulatory agencies: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Underwriters Laboratories listing. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | National Electrical Code. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Canadian Standards Association. | |||||||||||||||||||||||||||||||||||||||||||||||||
| C. | Certification: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Unheated Units: Units shall be tested in accordance with AMCA 220 and licensed to bear AMCA Certified Ratings Seal. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Heated Units: Except for inclusion of heating, units shall be tested in accordance with AMCA 220 and licensed to bear AMCA Certified Ratings Seal. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1.6 | DELIVERY, STORAGE, AND HANDLING | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Store products in manufacturer's unopened packaging until ready for installation. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Maintain dry, heated storage area for products until installation. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1.7 | SEQUENCING | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Coordinate the installation of wiring and control switches for air doors with the openings and the hardware provided for such openings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1.8 | WARRANTY | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Manufacturer's Warranty: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Supply manufacturer's standard two-year limited warranty for heated units against defects in workmanship and materials. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Supply manufacturer's standard five-year limited warranty for unheated units against defects in workmanship and materials. | |||||||||||||||||||||||||||||||||||||||||||||||||
| PART 2 | PRODUCTS | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2.1 | MANUFACTURERS | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Acceptable Manufacturer: Berner International Corp., which is located at: 111 Progress Ave. ; New Castle, PA 16101; Toll Free Tel: 800-245-4455; Tel: 724-658-3551; Fax: 724-652-0682; Email: request info; Web: www.berner.com | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Substitutions: Not permitted. | |||||||||||||||||||||||||||||||||||||||||||||||||
| C. | Requests for substitutions will be considered in accordance with provisions of Section 01600. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2.2 | AIR DOORS | |||||||||||||||||||||||||||||||||||||||||||||||||
Aristocrat-ASF is designed for customer entries up to 6 feet wide with door heights up to 9 feet for environmental separation and up to 8 feet for insect control. Aristocrat-ASF air doors can resist winds up to 10 MPH and are generally mounted inside building to recirculate warm air which has risen towards ceiling. Aristocrat-ASN meets requirements of NSF Standard 37 for doors 3 feet and 3-1/2 feet wide with door heights up to 7 feet for insect control. Aristocrat-ASR is designed for service doors up to 6 feet wide with door heights up to 10 feet for environmental separation and up to 9 feet for insect control. Aristocrat-ASR can resist winds up to 13 MPH and can be mounted inside or outside the building. Optimum protection is provided when units are mounted on inside of building, flush to the wall and as close to top of door opening as possible. To ensure peak performance keep air stream free of obstructions. Air doors may not be fully effective where negative air pressure exists on one side of door; contact Berner for additional information. Aristocrat models are standard with a 3/4 HP motor; an optional 1/2 HP motor is available. Aristocrat air doors can be wall mounted or suspended from the ceiling. Maximum recommended mounting height is 8 feet above floor. Electric heated unit should be installed indoors only and require a minimum clearance of 6 feet between the bottom of unit and floor and 4 inches between sides and top of the unit and any combustible material. A minimum of 4 inches is recommended above top for installation and removal of housing. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Acceptable Products: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Berner Model Aristocrat ASF. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Berner Model Aristocrat ASN. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Berner Model Aristocrat ASR. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Construction: Provide factory assembled units of sufficient structural strength to be supported from ends without intermediate support. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Cabinet: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Dimensions: Not to exceed 14-1/4 inches (36 mm) height by 13 inches (33 mm) deep. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Material: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Corrosion resistant Aluminum with polyester white on white painted finish. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Corrosion resistant Stainless Steel riveted construction, with stainless steel rivets. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Fasteners: Tamper-resistant type. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | Motor: Permanently lubricated and sealed bearings, double extended shafts, continuous duty, with internal thermal-overload protection. | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | 3/4 hp, ball bearings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | 1/2 hp, 3-speed, sleeve bearings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | Fans: Balanced forward curved type, double inlet, mounted in matched fan scrolls with aerodynamically formed air inlet venturies. | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Wheels and housing constructed of galvanized steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8. | Discharge Nozzle: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Provide uniform velocity across width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Aperture: 3-1/2 inches (9 mm) slot by width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Vanes: constructed of airfoil-shaped aluminum extrusions; air-directional vanes adjustable plus or minus 20 degrees to deflect airflow. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 9. | Air Intake: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Location: Front. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Screen: Perforated pattern constructed of the same material used in housing. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 10. | Filters: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Air intake filter re-cleanable aluminum with integral filter clips. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 11. | Heating Elements: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Electric Heating Coil: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | UL approved. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Factory-mounted, in factory-wired control compartment in galvanized steel frame, thermally protected. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Helical coil with point suspension of elements, single or three phase. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Thermal cutout locks out electric heaters when prolonged abnormal over-temperature conditions exist. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 12. | Controls: | |||||||||||||||||||||||||||||||||||||||||||||||||
Unheated 3/4 hp single speed - standard: switch not included. Unheated 1/2 hp three speed - standard: built-in, on-off, high-med-low switches. Electric heated 3/4 hp single speed - standard: built-in, fan-off-fan/heat switch. Electric 1/2 hp three speed - standard: built-in, fan-off-fan/heat, high-med-low switches. Select options required and delete those not required. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Switching: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Manual Switch: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Factory installed on/off switch. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Remote mount rotary cam hand-off-auto, 1-1/2 hp at 120V/1, 3 hp at 208V/1, 240V/1, or 480V/1. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Wall On/Off Switch and Cover Plate: single phase power only, rated for commercial use max 20 amps, mounted in a wall box. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Unheated Remote Fan Speed Selector Switch: three speed capacity; 1-1/2 hp at 120V/1 and 3 hp at 208V/1, 240V/1 or 480V/1. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Electric Heat Remote Fan Selector Switch: single speed capacity - 1-1/2 hp at 120V/1, 3 hp at 208V/1, 240V/1, or 480V/1. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5) | Electric Heat Remote Fan Speed Selector Switch: three speed capacity - 1-1/2 hp at 120V/1, 3 hp at 208V/1, 240V/1, or 480V/1. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6) | Automatic Door Switch: Switch automatically activates unit when door opens and deactivates unit when door closes. plunger type or roller arm. 120V, 208V, or 240V. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7) | Reed Switch: Magnetic, requires 24V transformer and time delay. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8) | Thermostat: Remote mount thermostat, capacity; 22 amps at 125/277 VAC. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 9) | Time Delay Relay: Adjustable in field from 0.1 second to 10 hour delay. Set delay for 2 minutes unless otherwise indicated. 120V, 208-240V, or 480V. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Damper plate: mounted on: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | One end of fan housing. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Both ends of fan housing. | |||||||||||||||||||||||||||||||||||||||||||||||||
At exterior openings, Aura air doors can resist winds up to 10 MPH and are generally mounted inside building to recirculate warm air which has risen towards ceiling. Air doors may not be fully effective where negative air pressure exists on one side of door; contact Berner for additional information. Model Aura has a 1/2 HP motor. It can be wall mounted, suspended from the ceiling or installed above the ceiling. Maximum recommended mounting height is 8 ft. above the floor. Electric heated unit should be installed indoors only and have a minimum clearance of at least 6 feet between the bottom of the unit and the floor and at least 4 inches between the sides and top of the unit and any combustible material. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Acceptable Product: Berner Model Aura. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Construction: Provide factory assembled units of sufficient structural strength to be supported from ends without intermediate support. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Cabinet: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Dimensions: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Not to exceed 28 inches (711 mm) height by 24 inches (610 mm) deep. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Not to exceed 28 inches (711 mm) height by 30 inches (762 mm) deep. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Rear adaptor: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Perforated grille. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Solid. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Solid with light kit using 10W halogen bulbs. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Finish: white powder coat textured finish. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Motors: Direct drive, 1600 rpm, 3 speed, resilient mounted, continuous duty, with internal thermal-overload protection. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Fans: Balanced forward curved type, double inlet, mounted in matched fan scrolls with aerodynamically formed air inlet venturies. | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Wheels and housings constructed of galvanized steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Discharge Nozzle: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Provide uniform velocity across width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Aperture: 2-1/2 inches (63 mm) slot by width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Vanes: 7/8 inch (22 mm) minimum high; constructed of airfoil-shaped aluminum extrusions; adjustable plus or minus 20 degrees to deflect airflow. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | Air Intake: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Location: Front. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Screen: Perforated steel intake grille. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Finish: White powder coat textured finish. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | Heating Elements: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Electric Heating Coil: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | UL approved. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Factory-mounted, factory-wired, galvanized steel frame, thermally protected. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Helical coil with point suspension of elements | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Single phase. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Three phase. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Thermal cutout: locks out electric heaters when prolonged abnormal over-temperature conditions exist. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8. | Controls: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Switching: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Remote Fan Speed Selector Switch: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | 1-1/2hp at 120V. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | 1 and 3 hp at 208V/1, 240V/1. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c) | Settings are high fan / medium fan / low fan / off. | |||||||||||||||||||||||||||||||||||||||||||||||||
| d) | Settings for electric heat; high fan / medium fan / low fan / off / high fan & heat / medium fan & heat / low fan & heat. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Automatic Door Switch: Switch automatically activates unit when door opens and deactivates unit when door closes. plunger type or roller arm. 120V/208V/240V. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Reed Switch: Magnetic, requires transformer. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Time Delay Relay: Adjustable in field from 0.1 second to 10 hours delay. Set delay for 2 minutes unless otherwise indicated. 120V/208-240V/480V. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5) | Thermostat: Remote mount factory installed thermostat, capacity; 22 amps at 125/277 VAC. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Thermostat Override: Switch prevents operation of heater when inside air temperature exceeds desired temperature.] | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Sequencing: [___________________________.] | |||||||||||||||||||||||||||||||||||||||||||||||||
Refer to product data and wind resistance charts in Berner product literature or website. Select specific models and sizes required for project and obtain data necessary to edit this specification. Edit specification to include only information specific to your project. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| C. | Acceptable Product: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Berner Model CFA with direct drive. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Berner Model CFC with direct drive. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Berner Model CFX with belt drive. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Berner Model CFY with belt drive. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Construction: Provide factory assembled units of sufficient structural strength to be supported from ends without intermediate support. Units shall have split cabinet with removable lower section for access to internal components. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | Cabinet: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Minimum 14 gauge aluminized steel with baked enamel finish. Color as selected by the Architect from manufacturers standard colors. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Minimum 14 gauge stainless steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | All welded construction. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | Motors: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Direct Drive: 1,160 RPM, totally enclosed air over (TEAO). | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Belt Drive: 1,750 RPM, totally enclosed fan cooled (TEFC). | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8. | Fans: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Balance forward curved centrifugal type, double inlet, double width design with welded hubs, mounted in matched fan housings with aerodynamically formed air inlet venturies. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Wheels and housings constructed of galvanized steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Blower wheels driven through flexible couplings. Each blower wheel supported by two permanently lubricated 1 inch (25.4 mm) sealed ball bearings encased in vibration isolating rubber cartridges. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 9. | Discharge Nozzle: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Provides uniform velocity across width of air door. Shall be mounted on continuous piano hinge to allow 3-way deflection of air stream plus or minus 20 degrees without loss of discharge velocity or opening area. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Aperture: 4-1/2 inches (114.3 mm) by width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Vanes: 3/4 inches (19.05 mm) minimum height; constructed of airfoil-shaped aluminum extrusions. | |||||||||||||||||||||||||||||||||||||||||||||||||
| d. | Air volume control damper. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 10. | Air Intake: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Location: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Top. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Front. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Screen: Expanded metal with welded frame. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 11. | Air Inlet Filter: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Flat-faced type, disposable. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | V-bank type, disposable. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Re-cleanable aluminum with integral filter clips. | |||||||||||||||||||||||||||||||||||||||||||||||||
| d. | Re-cleanable stainless steel with hinged inlet screen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 12. | Heating Elements: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Electric Heating Coil: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | UL approved. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Factory-mounted, in factory-wired control compartment. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Automatic reset limit control, manual reset limit control, primary magnetic contactors, air flow switch, power terminal board, equipment grounding lug, power fusing, and control transformer. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Steam Coil: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Certify per ARI 410. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Construction: 5/8 inch (15.8 mm) outside diameter copper tube with aluminum fins. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Characteristics: Design to operate at maximum 150 psig (1,035 kPa) and 366 degree F (185 degrees C) steam. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Leak-test under water at 350 psig (2410 kPa) dry nitrogen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5) | Factory mounted on air intake, protected by expanded metal screen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Hot Water Coil: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Certify per ARI 410. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Construction: 5/8 inch (15.8 mm) outside diameter copper tube with aluminum fins. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Characteristics: Design to operate at maximum 250 psig (1,720 kPa) and 300 degree F (149 degrees C) hot water. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Leak-test under water at 350 psig (2,410 kPa) dry nitrogen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5) | Factory mounted on air intake, protected by expanded metal screen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| d. | Indirect Gas Heater and Duct Transition: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | American Gas Association (AGA) or Canadian Gas Association (CGA) labeled. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Fuel Type: Provide orifices for: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Natural gas. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | LP. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Heat Exchanger and Burner: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Aluminized steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Stainless steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Characteristics: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | 120 volt Separate supply voltage, power exhaust vent, 120 volt limit control, 24 volt control voltage transformer, combustion air pressure switch, spark ignited intermittent safety pilot system with electronic flame supervision. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | 120 volt Single Point supply voltage, power exhaust vent, 120 volt limit control, 24 volt control voltage transformer, combustion air pressure switch, spark ignited intermittent safety pilot system with electronic flame supervision. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5) | Independently support each heater at least 1 inch (25 mm) from each opening of factory-installed duct transition. Duct transition constructed of 16 gauge aluminized steel with access panels spanning entire width. | |||||||||||||||||||||||||||||||||||||||||||||||||
| e. | Direct Gas Fired Heater: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Fuel Type: Natural Gas. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Characteristics: Provide minimum turndown ratio of 30:1 stainless steel baffles, non-clogging orifices, ignition system, flame safeguard, gas manifold, valves, and temperature controls. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Gas Manifold (Train): As required by governing authority. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Spark ignited intermittent pilot. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 13. | Controls: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Control Panel: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | UL listed, industrial type, pre-wired, with components consisting of motor starter, terminal strip, motor overloads, control transformer with 120 or 24 volt fused secondary. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Single power supply. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Separate power supply. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Enclosure: Oil-tight and dust-tight NEMA enclosure with neoprene door gasket: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Type 4 | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Type 12 | |||||||||||||||||||||||||||||||||||||||||||||||||
| c) | Type 13 | |||||||||||||||||||||||||||||||||||||||||||||||||
| d) | Type 4X | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5) | Mounting: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Remote mounted as indicated on Drawings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Unit mounted right end. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c) | Unit mounted left end. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6) | Time Delay Relay: Adjustable in field from 0.1 second to 10 hours delay. Set delay for 1 minute unless otherwise indicated. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7) | Disconnect Switch: Provide lockable, disconnect switch in control panel. Disconnect shall be: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Fused | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Non-fused | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8) | ON-OFF-AUTOMATIC Switch: Switch allows manual on-off operation or operation controlled by automatic door switch that activates unit when door opens and deactivates unit when door closes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 9) | Manual Switch: Provide ON-OFF push button operation. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 10) | Heat-On-Off. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Single Phase Control Station: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | UL listed, industrial type, pre-wired, with UL-listed components consisting of motor starter and terminal strip. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Enclosure: Oil-tight and dust-tight NEMA enclosure with neoprene door gasket: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Type 4 | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Type 12 | |||||||||||||||||||||||||||||||||||||||||||||||||
| c) | Type 13 | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Mounting: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Remote mounted as indicated on Drawings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Unit mounted right end. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c) | Unit mounted left end. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Time Delay Relay: Adjustable in field from 0.1 second to 10 hours delay. Set delay for 1 minute unless otherwise indicated. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Dry-type distribution transformer. | |||||||||||||||||||||||||||||||||||||||||||||||||
| d. | Remote Activation Devices: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Automatic Door Switch: Switch automatically activates unit when door opens and deactivates unit when door is closes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | ON-OFF-AUTOMATIC Switch: Switch allows manual on-off operation or operation controlled by automatic door switch that activates unit when door opens and deactivates unit when door closes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Manual Switch: Provide ON-OFF push button operation. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Heat-On-Off. | |||||||||||||||||||||||||||||||||||||||||||||||||
| e. | Thermostat: Prevents operation of heater when inside air temperature exceeds desired temperature. | |||||||||||||||||||||||||||||||||||||||||||||||||
| D. | Acceptable Products: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Berner Model KSA. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Berner Model KSB. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Construction: Provide factory assembled units of sufficient structural strength to be supported from ends without intermediate support. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Cabinet: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Material: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Minimum 16 gauge aluminized steel with powder coat finish and aluminum inlet screen, all welded construction. Color as selected by the Architect from the manufacturers standard colors. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Minimum 16 gauge stainless steel, all welded construction. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Tamper-resistant construction. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Mounting: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Provisions for top or wall mounting. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Provisions for tandem mounting (vertical only). | |||||||||||||||||||||||||||||||||||||||||||||||||
| d. | Removable top and bottom panels for access. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Motors: 1,750 RPM, double extended shafts with sealed bearings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | 1 speed. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | Fans: Balanced forward curved centrifugal type, double inlet, double width design, mounted in matched fan housings with aerodynamically formed air inlet venturies. | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Construct wheels and housings constructed of galvanized steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | Discharge Nozzle: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Provide uniform velocity across width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Aperture: 3-1/2 inches (63.5 mm) by width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Vanes: 1-1/2 inches (38 mm) minimum height; constructed of airfoil-shaped aluminum extrusions; adjustable plus or minus 20 degrees to deflect air flow. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8. | Air Volume Control Damper. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 9. | Air Intake: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Location: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Front. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Top. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Screen: Perforated metal with border. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Mill aluminum. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Stainless steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 10. | Air Inlet Filter: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Flat-faced type, disposable. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Flat-Faced, re-cleanable aluminum. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Flat-Faced, re-cleanable stainless steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| d. | Provide without screen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| e. | Provide with screen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 11. | Heating Elements: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Electric Heating Coil: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | UL approved. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Factory-mounted, with factory-wired control compartment. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Automatic reset limit control, manual reset limit control, primary magnetic contactors, air flow switch, power terminal board, equipment grounding lug, power fusing, and control transformer. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 12. | Controls: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Control Panel: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | UL listed, industrial type, pre-wired, with components consisting of motor starter, terminal strip, motor overloads, control transformer with 120 or 24 volt fused secondary. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Single power supply. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Separate power supply. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Enclosure: Oil-tight and dust-tight NEMA enclosure with neoprene door gasket: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Type 4 | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Type 12 | |||||||||||||||||||||||||||||||||||||||||||||||||
| c) | Type 13 | |||||||||||||||||||||||||||||||||||||||||||||||||
| d) | Type 4X | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5) | Mounting: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Remote mounted as indicated on Drawings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Unit mounted right end. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c) | Unit mounted left end. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6) | Time Delay Relay: Adjustable in field from 0.1 second to 10 hours delay. Set delay for 1 minute unless otherwise indicated. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7) | Disconnect Switch: Provide lockable, disconnect switch in control panel. Disconnect shall be: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Fused | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Non-fused | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8) | ON-OFF-AUTOMATIC Switch: Switch allows manual on-off operation or operation controlled by automatic door switch that activates unit when door opens and deactivates unit when door closes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 9) | Manual Switch: Provide ON-OFF push button operation. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 10) | Heat-On-Off. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Single Phase Control Station: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | UL listed, industrial type, pre-wired, with UL-listed components consisting of motor starter and terminal strip. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Enclosure: Oil-tight and dust-tight NEMA enclosure with neoprene door gasket: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Type 4 | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Type 12 | |||||||||||||||||||||||||||||||||||||||||||||||||
| c) | Type 13 | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Mounting: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Remote mounted as indicated on Drawings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Unit mounted right end. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c) | Unit mounted left end. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Time Delay Relay: Adjustable in field from 0.1 second to 10 hours delay. Set delay for 1 minute unless otherwise indicated. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Remote Activation Devices: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Automatic Door Switch: Switch automatically activates unit when door opens and deactivates unit when door is closes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | ON-OFF-AUTOMATIC Switch: Switch allows manual on-off operation or operation controlled by automatic door switch that activates unit when door opens and deactivates unit when door closes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Manual Switch: Provide ON-OFF push button operation. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Heat-On-Off. | |||||||||||||||||||||||||||||||||||||||||||||||||
| d. | Thermostat: Prevents operation of heater when inside air temperature exceeds desired temperature. | |||||||||||||||||||||||||||||||||||||||||||||||||
At exterior openings, air doors can resist winds up to 12 MPH and are generally mounted inside building to recirculate warm air, which has risen towards ceiling. Air doors may not be fully effective where negative air pressure exists on one side of door; contact Berner for additional information. Model Diplomat II has 1/2 HP motors. It can be wall mounted, suspended from the ceiling or installed above the ceiling. Electric heated unit should be installed indoors only and have a minimum clearance of at least 6 feet between the bottom of the unit and the floor and at least 1 inch between the sides and top of the unit and any combustible material. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| E. | Acceptable Products: Berner Model Diplomat II. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Construction: Provide factory assembled units of sufficient structural strength to be supported from ends without intermediate support. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Cabinet: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Dimensions: Not to exceed 12-1/4 inches (311 mm) high by 22 inches (559 mm) deep. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Clear anodized aluminum. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Bronze. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Stainless steel | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Aluminum with baked enamel finish, color as selected by the Architect from the manufacturers standard colors. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Fasteners: Tamper-resistant type. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Motors: Direct driven, 1600 rpm, three speed resilient mounted, continuous duty, with internal thermal-overload protection and sealed sleeve bearing permanently lubricated. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Fans: Balanced forward curved type, double inlet, mounted in matched fan scrolls with aerodynamically formed air inlet venturies. | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Construct wheels and housings constructed of galvanized steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Discharge Nozzle: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Provide uniform velocity across width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Aperture: 2-1/2 inches (63 mm) slot by width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Vanes: 1-1/2 inches (38 mm) minimum height; constructed of airfoil-shaped aluminum extrusions; locking air-directional vanes adjustable plus or minus 20 degrees to deflect airflow. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | Nozzle Extension: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Unpainted aluminized steel with airfoil shaped anodized aluminum discharge vanes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Anodized aluminum with airfoil shaped anodized aluminum discharge vanes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Anodized aluminum with airfoil shaped white aluminum multi-blade air discharge grille. | |||||||||||||||||||||||||||||||||||||||||||||||||
| d. | Unpainted aluminized steel with airfoil shaped white aluminum multi-blade air discharge grille. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | Air Intake: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Location: Front. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Screen: Perforated aluminum with extruded aluminum frame. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Filter: provide recleanable filter for each intake screen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8. | Heating Elements: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Electric Heating Coil: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | UL approved. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Factory-mounted, factory-wired, galvanized steel frame, thermally protected. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Helical coil with point suspension of elements: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Single phase. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Three phase. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Thermal cutout: locks out electric heaters when prolonged abnormal over-temperature conditions exist. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Steam/Hot Water Coil: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Certify per ARI 410. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Construction: 16 gauge galvanized steel casing, 5/8 inches (15.8 mm) outside diameter copper steam/hot water coil with aluminum fins and seamless copper headers. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Leak-test at Steam 325 psig (2238 kPa), Hot Water 350 psig (2415 kPa) dry nitrogen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Factory mount on air door intake, protected by perforated metal screen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 9. | Controls: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Switching: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Manual Switch: factory installed, three speed control switch with on/off switch. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Automatic Door Switch: Switch automatically activates unit when door opens and deactivates unit when door closes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Plunger type. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Roller arm. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Reed Switch: Magnetic, requires transformer & time delay. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Time Delay Relay: Adjustable in field from 0.1 second to 10 hours delay. Set delay for 2 minutes unless otherwise indicated. | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | 24V | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | 120V | |||||||||||||||||||||||||||||||||||||||||||||||||
| c) | 208-240V | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5) | Disconnect Switch: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | 30 Amp 1 phase. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | 30 Amp 3 phase. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c) | 40 Amp 3 phase. | |||||||||||||||||||||||||||||||||||||||||||||||||
| d) | 60 Amp 3 phase. | |||||||||||||||||||||||||||||||||||||||||||||||||
Optional for unheated or steam/hot water air doors with these settings: high fan / medium fan / low fan / off. Optional for electric heat with these settings; high fan / medium fan / low fan / off / high fan & heat / medium fan & heat / low fan & heat. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| 6) | Remote Fan Speed Selector Switch: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | 1-1/2hp at 120V/1 | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | 3 hp at 208V/1, 240V/1 | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7) | Thermostat: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Remote mount, thermostat, capacity; 22 amps at 125/277 VAC. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Factory installed, thermostat, capacity; 22 amps at 125/277 VAC. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Thermostat Override: Switch prevents operation of heater when inside air temperature exceeds desired temperature. | |||||||||||||||||||||||||||||||||||||||||||||||||
At exterior openings, air doors can resist winds up to 8 MPH and are generally mounted inside building to recirculate warm air, which has risen towards ceiling. Air doors may not be fully effective where negative air pressure exists on one side of door; contact Berner for additional information. Model E-ZONE has 1/5 HP motors. E-ZONE can be wall mounted or suspended from the ceiling. Maximum recommended mounting height is 8 feet above the floor. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| F. | Acceptable Products: Berner Model E-ZONE. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Construction: Provide factory-assembled units of sufficient structural strength to be supported from ends without intermediate support. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Cabinet: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Dimensions: Not to exceed 8-1/2 inches (216 mm) height by 8 inches (203 mm) deep. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Material: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Aluminized steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Stainless steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Riveted construction, with stainless steel rivets. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Motors: direct drive, 1600 rpm, resilient mounted, continuous duty, with internal thermal-overload protection and permanently lubricated sealed sleeve bearings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Fans: Balanced forward curved cross flow, tangential type with flexible hubs, made of aluminum, mounted in matched fan scrolls constructed of material used in cabinet. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Discharge Nozzle: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Provide uniform velocity across width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Aperture: 2.375 inches (60.325 mm) slot by width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Vanes: 1-1/2 inches (38 mm) minimum high; constructed of airfoil-shaped aluminum extrusions; adjustable plus or minus 20 degrees to deflect airflow. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | Inlet: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Location: Front. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Screen: Perforated pattern constructed of the same material used in housing. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | Controls: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Switching: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Factory installed variable speed control switch. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Control Accessories: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Reed Switch: Magnetic with 24V load center. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Plunger Door Switch: 120/208/240V. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Manual Switch: Provide START-STOP operation. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Sequencing: [___________________________.] | |||||||||||||||||||||||||||||||||||||||||||||||||
At exterior openings, air doors can resist winds up to 30 MPH and are generally mounted inside building to recirculate warm air that has risen towards ceiling. They can also be used at interior openings (e.g., ovens, paint-spray rooms, clean rooms) to prevent interchange of heat, fumes, dust, and humidity. Air doors may not be fully effective where negative air pressure exists on one side of door; contact Berner for additional information. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| G. | Acceptable Products: Berner Model EWD. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Construction: Provide factory assembled units of sufficient structural strength to be supported from ends without intermediate support. Unit shall have split housing with fans contained within a removable casing. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Cabinet: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Minimum 14 gage galvanized steel with baked enamel finish, color as selected by the Architect from the manufacturers standard colors. Welded construction. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Minimum 14 gage stainless steel, welded construction. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Motors: 1,750 RPM, totally enclosed fan cooled (TEFC). Motors shall be located outside air stream. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Fans: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Balanced forward curved centrifugal type, double inlet, double width design with welded hubs, mounted in matched fan housings with aerodynamically formed inlet cones. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Wheels and housings constructed of heavy gage galvanized steel or epoxy enamel finish. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Blower wheels shall be driven through flexible couplings. Each blower wheel shall be supported by heavy duty pillow-block bearings with grease fittings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Discharge Nozzle: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Provides uniform velocity across width of air door. Shall be equipped with aerodynamically shaped airfoil air direction vane to allow deflection of entire air stream plus or minus 20 degrees without loss of discharge velocity or opening area | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Aperture: 8.00 inches (203 mm) by width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | Air Intake: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Location: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Top. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Front. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Screen: Expanded metal with welded frame. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | Heating Elements: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Steam Coil: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Certify per ARI 410. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Construction: 5/8 inch (15.8 mm) outside diameter copper tube with aluminum fins. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Characteristics: Design to operate at maximum 150 psig (1,035 kPa) and 366 degree F (185 degrees C) steam. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Leak-test under water at 350 psig (2410 kPa) dry nitrogen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5) | Factory mounted on air intake, protected by expanded metal screen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Hot Water Coil: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Certify per ARI 410. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Construction: 5/8 inch (15.8 mm) outside diameter copper tube with aluminum fins. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Characteristics: Design to operate at maximum 250 psig (1,720 kPa) and 300 degree F (149 degrees C) hot water. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Leak-test under water at 350 psig (2,410 kPa) dry nitrogen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5) | Factory mounted on air intake, protected by expanded metal screen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Indirect Gas Heater and Duct Transition: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | American Gas Association (AGA) or Canadian Gas Association (CGA) labeled. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Fuel Type: Provide orifices for: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Natural gas. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | LP. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Heat Exchanger and Burner: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Aluminized steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Stainless steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Characteristics: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | 120 volt Separate supply voltage, power exhaust vent, 120 volt limit control, 24 volt control voltage transformer, combustion air pressure switch, spark ignited intermittent safety pilot system with electronic flame supervision. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | 120 volt Single Point supply voltage, power exhaust vent, 120 volt limit control, 24 volt control voltage transformer, combustion air pressure switch, spark ignited intermittent safety pilot system with electronic flame supervision. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5) | Independently support each heater at least 1 inch (25 mm) from each opening of factory-installed duct transition. Duct transition constructed of 16 gauge aluminized steel with access panels spanning entire width. | |||||||||||||||||||||||||||||||||||||||||||||||||
| d. | Direct Gas Fired Heater: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Fuel Type: Natural Gas. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Characteristics: Provide minimum turndown ratio of 30:1 stainless steel baffles, non-clogging orifices, ignition system, flame safeguard, gas manifold, valves, and temperature controls. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Gas Manifold (Train): As required by governing authority. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Spark ignited intermittent pilot. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8. | Controls: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Control Panel: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | UL listed, industrial type, pre-wired, with components consisting of motor starter, terminal strip, motor overloads, control transformer with 120 or 24 volt fused secondary. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Single power supply. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Separate power supply. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Enclosure: Oil-tight and dust-tight NEMA enclosure with neoprene door gasket: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Type 4 | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Type 12 | |||||||||||||||||||||||||||||||||||||||||||||||||
| c) | Type 13 | |||||||||||||||||||||||||||||||||||||||||||||||||
| d) | Type 4X | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5) | Mounting: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Remote mounted as indicated on Drawings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Unit mounted right end. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c) | Unit mounted left end. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6) | Time Delay Relay: Adjustable in field from 0.1 second to 10 hours delay. Set delay for 1 minute unless otherwise indicated. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7) | Disconnect Switch: Provide lockable, disconnect switch in control panel. Disconnect shall be: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Fused | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Non-fused | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8) | ON-OFF-AUTOMATIC Switch: Switch allows manual on-off operation or operation controlled by automatic door switch that activates unit when door opens and deactivates unit when door closes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 9) | Manual Switch: Provide ON-OFF push button operation. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 10) | Heat-On-Off. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Single Phase Control Station: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | UL listed, industrial type, pre-wired, with UL-listed components consisting of motor starter and terminal strip. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Enclosure: Oil-tight and dust-tight NEMA enclosure with neoprene door gasket: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Type 4 | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Type 12 | |||||||||||||||||||||||||||||||||||||||||||||||||
| c) | Type 13 | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Mounting: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Remote mounted as indicated on Drawings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Unit mounted right end. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c) | Unit mounted left end. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Time Delay Relay: Adjustable in field from 0.1 second to 10 hours delay. Set delay for 1 minute unless otherwise indicated. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Dry-type distribution transformer | |||||||||||||||||||||||||||||||||||||||||||||||||
| d. | Remote Activation Devices: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Automatic Door Switch: Switch automatically activates unit when door opens and deactivates unit when door is closes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | ON-OFF-AUTOMATIC Switch: Switch allows manual on-off operation or operation controlled by automatic door switch that activates unit when door opens and deactivates unit when door closes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Manual Switch: Provide ON-OFF push button operation. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Heat-On-Off. | |||||||||||||||||||||||||||||||||||||||||||||||||
| e. | Thermostat: Prevents operation of heater when inside air temperature exceeds desired temperature. | |||||||||||||||||||||||||||||||||||||||||||||||||
| f. | Sequencing: ___________________________. | |||||||||||||||||||||||||||||||||||||||||||||||||
| H. | Acceptable Products: Berner Model FS. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Construction: Provide factory assembled units of sufficient structural strength to be supported from ends without intermediate support. One pair of heavy duty mounting brackets shall be included. Mounting brackets shall permit adjustment of air stream discharge angel of plus or minus 20 degrees degrees. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Cabinet: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Material: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Minimum 14 gauge aluminized steel with baked enamel finish, color as selected by the Architect from the manufacturers standard colors, all welded construction. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Minimum 14 gauge stainless steel, all welded construction. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Fasteners: Tamper-resistant type. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Motors: 1,725 RPM, totally enclosed air over (TEAO) direct drive motors. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Fans: Fans shall be 24 inches diameter, four blade propeller type with inlet venturi. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Discharge Nozzle: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Nozzle provides uniform velocity across width of air stream | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Aperture: 5.00 inches (127 mm) slot by width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | Inlet: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Location: Top. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Screen: Fan guard. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | Weather Hood: Steel. Provide one per fan. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8. | Controls: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Control Panel: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | UL listed, industrial type, pre-wired, with components consisting of motor starter, terminal strip, motor overloads, control transformer with 120 or 24 volt fused secondary. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Enclosure: Oil-tight and dust-tight NEMA Type 4 enclosure with neoprene door gasket. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Mounting: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Remote mounted as indicated on Drawings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Unit mounted. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Disconnect Switch: Provide lockable, disconnect switch in control panel. Disconnect shall be: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Fused | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Non-fused | |||||||||||||||||||||||||||||||||||||||||||||||||
| d. | Switching: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Automatic Door Switch: Switch automatically activates unit when door opens and deactivates unit when door is closes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Combination ON-OFF-AUTOMATIC Switch: One on-off-automatic switch and one automatic door switch shall be remotely mounted in door area. On-off-automatic switch, when in ON position, shall activate unit whether door is opened or closed. In OFF position, unit shall not operate. In AUTOMATIC position, unit shall automatically activate each time door is open, and deactivate each time door is closed. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Manual Switch: Provide START-STOP push button operation. | |||||||||||||||||||||||||||||||||||||||||||||||||
At exterior openings, air doors can resist winds up to 8 MPH and are generally mounted inside building to recirculate warm air which has risen towards the ceiling. They can also be used at interior openings (e.g., ovens, paint-spray rooms, clean rooms) to prevent interchange of heat, fumes, dust, and humidity. Air doors may not be fully effective where negative air pressure exists on one side of door; contact Berner for additional information. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| I. | Acceptable Products: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Berner Model VSA. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Berner Model VSB. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Construction: Provide factory assembled units of sufficient structural strength to be supported from ends without intermediate support. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Cabinet: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Material: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Minimum 16 gauge aluminized steel with powder coat finish, aluminum inlet screen, all welded construction. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Minimum 16 gauge stainless steel, all welded construction. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Mounting: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Provisions for top or wall mounting. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Provisions for tandem mounting (vertical only). | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Removable bottom panel for access. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Motors: 1,750 RPM, double extended shafts with sealed bearings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | 1 speed. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | 2 speed. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | Fans: Balanced forward curved centrifugal type, double inlet, double width design, mounted in matched fan housings with aerodynamically formed air inlet venturies. | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Construct wheels and housings constructed of galvanized steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | Discharge Nozzle: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Provide uniform velocity across width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Aperture: 3-1/2 inches (63.5 mm) by width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Vanes: 1-1/2 inches (38 mm) minimum height; constructed of airfoil-shaped aluminum extrusions; adjustable plus or minus 20 degrees to deflect air flow. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8. | Air Volume Control Damper. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 9. | Air Intake: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Location: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Front. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Top. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Screen: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Perforated mill aluminum with border. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Perforated stainless steel with border. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 10. | Air Inlet Filter: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Flat-faced type, disposable. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Flat-Faced, re-cleanable aluminum. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Flat-Faced, re-cleanable stainless steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 11. | Heating Elements: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Electric Heating Coil: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | UL approved. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Factory-mounted, with factory-wired control compartment. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Automatic reset limit control, manual reset limit control, primary magnetic contactors, air flow switch, power terminal board, equipment grounding lug, power fusing, and control transformer. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Steam Coil: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Certify per ARI 410. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Construction: 5/8 inch (15.8 mm) outside diameter copper tube with aluminum fins. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Characteristics: Design to operate at maximum 150 psig (1,035 kPa) and 366 degree F (185 degrees C) steam. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Leak-test under water at 350 psig (2410 kPa) dry nitrogen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5) | Factory mounted on air intake, protected by expanded metal screen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Hot Water Coil: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Certify per ARI 410. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Construction: 5/8 inch (15.8 mm) outside diameter copper tube with aluminum fins. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Characteristics: Design to operate at maximum 250 psig (1,720 kPa) and 300 degree F (149 degrees C) hot water. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Leak-test under water at 350 psig (2,410 kPa) dry nitrogen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5) | Factory mounted on air intake, protected by expanded metal screen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| d. | Indirect Gas Heater and Duct Transition: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | American Gas Association (AGA) or Canadian Gas Association (CGA) labeled. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Fuel Type: Provide orifices for: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Natural gas. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | LP. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Heat Exchanger and Burner: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Aluminized steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Stainless steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Characteristics: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | 120 volt Separate supply voltage, power exhaust vent, 120 volt limit control, 24 volt control voltage transformer, combustion air pressure switch, spark ignited intermittent safety pilot system with electronic flame supervision. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | 120 volt Single Point supply voltage, power exhaust vent, 120 volt limit control, 24 volt control voltage transformer, combustion air pressure switch, spark ignited intermittent safety pilot system with electronic flame supervision. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5) | Independently support each heater at least 1 inch (25 mm) from each opening of factory-installed duct transition. Duct transition constructed of 16 gauge aluminized steel with access panels spanning entire width. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 12. | Controls: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Control Panel: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | UL listed, industrial type, pre-wired, with components consisting of motor starter, terminal strip, motor overloads, control transformer with 120 or 24 volt fused secondary. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Single power supply. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Separate power supply. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Enclosure: Oil-tight and dust-tight NEMA enclosure with neoprene door gasket: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Type 4 | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Type 12 | |||||||||||||||||||||||||||||||||||||||||||||||||
| c) | Type 13 | |||||||||||||||||||||||||||||||||||||||||||||||||
| d) | Type 4X | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5) | Mounting: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Remote mounted as indicated on Drawings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Unit mounted right end. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c) | Unit mounted left end. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6) | Time Delay Relay: Adjustable in field from 0.1 second to 10 hours delay. Set delay for 1 minute unless otherwise indicated. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7) | Disconnect Switch: Provide lockable, disconnect switch in control panel. Disconnect shall be: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Fused | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Non-fused | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8) | ON-OFF-AUTOMATIC Switch: Switch allows manual on-off operation or operation controlled by automatic door switch that activates unit when door opens and deactivates unit when door closes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 9) | Manual Switch: Provide ON-OFF push button operation. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 10) | Heat-On-Off. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Single Phase Control Station: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | UL listed, industrial type, pre-wired, with UL-listed components consisting of motor starter and terminal strip. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Enclosure: Oil-tight and dust-tight NEMA enclosure with neoprene door gasket: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Type 4 | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Type 12 | |||||||||||||||||||||||||||||||||||||||||||||||||
| c) | Type 13 | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Mounting: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Remote mounted as indicated on Drawings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Unit mounted right end. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c) | Unit mounted left end. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Time Delay Relay: Adjustable in field from 0.1 second to 10 hours delay. Set delay for 1 minute unless otherwise indicated. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Dry-type distribution transformer | |||||||||||||||||||||||||||||||||||||||||||||||||
| d. | Remote Activation Devices: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Automatic Door Switch: Switch automatically activates unit when door opens and deactivates unit when door is closes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | ON-OFF-AUTOMATIC Switch: Switch allows manual on-off operation or operation controlled by automatic door switch that activates unit when door opens and deactivates unit when door closes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Manual Switch: Provide ON-OFF push button operation. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Heat-On-Off. | |||||||||||||||||||||||||||||||||||||||||||||||||
| e. | Thermostat: Prevents operation of heater when inside air temperature exceeds desired temperature. | |||||||||||||||||||||||||||||||||||||||||||||||||
| f. | Sequencing: ___________________________. | |||||||||||||||||||||||||||||||||||||||||||||||||
At exterior openings, air doors can resist winds up to 8 MPH and are generally mounted inside building to recirculate warm air, which has risen towards ceiling. Air doors may not be fully effective where negative air pressure exists on one side of door; contact Berner for additional information. Model K-ZONE has 1/5 HP motors. K-ZONE can be wall mounted or suspended from the ceiling. Maximum recommended mounting height is 8 feet above the floor. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| J. | Acceptable Products: Berner Model K-ZONE. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Construction: Provide factory-assembled units of sufficient structural strength to be supported from ends without intermediate support. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Cabinet: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Dimensions: Not to exceed 8-1/2 inches (216 mm) height by 8 inches (203 mm) deep. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Material: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Aluminized steel riveted construction, with stainless steel rivets. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Stainless steel riveted construction, with stainless steel rivets. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Motors: direct drive, 1600 rpm, resilient mounted, continuous duty, with internal thermal-overload protection and permanently lubricated sealed sleeve bearings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Fans: Balanced forward curved cross flow, tangential type with flexible hubs, made of aluminum, mounted in matched fan scrolls constructed of material used in cabinet. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Discharge Nozzle: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Provide uniform velocity across width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Aperture: 2.375 inches (60.325 mm) slot by width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Vanes: 1-1/2 inches (38 mm) minimum high; constructed of airfoil-shaped aluminum extrusions; adjustable plus or minus 20 degrees to deflect airflow. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | Inlet: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Location: Front. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Screen: Perforated pattern constructed of the same material used in housing. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | Controls: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Switching: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Factory installed variable speed control switch. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Control Accessories: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Reed Switch: Magnetic with 24V load center. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Plunger Door Switch: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | 120V. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | 208/240V. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Manual disconnect switch. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Manual Switch: Provide START-STOP operation. | |||||||||||||||||||||||||||||||||||||||||||||||||
At exterior openings, air doors can resist winds up to 12 MPH and are generally mounted inside building to recirculate warm air, which has risen towards ceiling. Air doors may not be fully effective where negative air pressure exists on one side of door; contact Berner for additional information. Model Mark II has 1/2 HP motors. It can be wall mounted, suspended from the ceiling or installed above the ceiling. Electric heated unit should be installed indoors only and have a minimum clearance of at least 6 feet between the bottom of the unit and the floor and at least 1 inch between the sides and top of the unit and any combustible material. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| K. | Acceptable Products: Berner Model Mark II. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Construction: Provide factory assembled units of sufficient structural strength to be supported from ends without intermediate support. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Cabinet: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Dimensions: Not to exceed 12-1/4 inches (311 mm) high by 22 inches (559 mm) deep. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Material and Finish: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Clear anodized aluminum. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Bronze. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Stainless steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Aluminum with baked enamel finish, color as selected by the Architect from the manufacturers standard colors. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Fasteners: Tamper-resistant type. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Motors: direct driven, 1600 rpm, three speed resilient mounted, continuous duty, with internal thermal-overload protection and sealed sleeve bearing permanently lubricated. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Fans: Balanced forward curved type, double inlet, mounted in matched fan scrolls with aerodynamically formed air inlet venturies. | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Wheels and housings constructed of galvanized steel | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Discharge Nozzle: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Provide uniform velocity across width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Aperture: 2-1/2 inches (63 mm) slot by width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Vanes: 1-1/2 inches (38 mm) minimum height; constructed of airfoil-shaped aluminum extrusions; locking air-directional vanes adjustable plus or minus 20 degrees to deflect airflow. | |||||||||||||||||||||||||||||||||||||||||||||||||
| d. | Recommend for all heated and unheated systems installed above a ceiling. Provided 21 inches (533 mm) high suitable for field cutting to length. Aluminum air directional vanes standard, white aluminum multi-blade air discharge grille optional. | |||||||||||||||||||||||||||||||||||||||||||||||||
| e. | Nozzle Extension: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Unpainted aluminized steel with airfoil shaped anodized aluminum discharge vanes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Unpainted aluminized steel with airfoil shaped white aluminum multi-blade air discharge grille. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Anodized aluminum with airfoil shaped anodized aluminum discharge vanes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Anodized aluminum with airfoil shaped white aluminum multi-blade air discharge grille. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | Air Intake: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Location: Front. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Screen: Perforated aluminum with extruded aluminum frame. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Filter: provide recleanable filter for each intake screen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | Heating Elements: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Electric Heating Coil: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | UL approved. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Factory-mounted, factory-wired, galvanized steel frame, thermally protected. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Helical coil with point suspension of elements: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Single. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Three phase. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Thermal cutout: locks out electric heaters when prolonged abnormal over-temperature conditions exist. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Steam/Hot Water Coil: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Certify per ARI 410. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Construction: 16 gauge galvanized steel casing, 5/8 inch (15.8 mm) outside diameter copper steam/hot water coil with aluminum fins and seamless copper headers. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Leak-test at Steam 325 psig (2238 kPa), Hot Water 350 psig (2415 kPa) dry nitrogen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Factory mount on air door intake, protected by perforated metal screen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8. | Controls: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Switching: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Manual Switch: factory installed, three speed control switch with on/off switch. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Automatic Door Switch: Switch automatically activates unit when door opens and deactivates unit when door closes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Plunger type. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Roller arm. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Reed Switch: Magnetic, requires transformer & time delay. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Time Delay Relay: Adjustable in field from 0.1 second to 10 hours delay. Set delay for 2 minutes unless otherwise indicated. | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | 24V | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | 120V | |||||||||||||||||||||||||||||||||||||||||||||||||
| c) | 208-240V | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5) | Disconnect Switch: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | 30 Amp 1 phase. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | 30 Amp 3 phase. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c) | 40 Amp 3 phase. | |||||||||||||||||||||||||||||||||||||||||||||||||
| d) | 60 Amp 3 phase. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6) | 6. Remote Fan Speed Selector Switch: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | 1-1/2hp at 120V/1 | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | 3 hp at 208V/1, 240V/1 | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7) | Thermostat: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Remote mount, thermostat, capacity; 22 amps at 125/277 VAC. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Factory installed, thermostat, capacity; 22 amps at 125/277 VAC. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Thermostat Override: Switch prevents operation of heater when inside air temperature exceeds desired temperature. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Sequencing: ___________________________. | |||||||||||||||||||||||||||||||||||||||||||||||||
At exterior openings, air doors can resist winds up to 8 MPH and are generally mounted inside building to recirculate warm air, which has risen towards ceiling. Air doors may not be fully effective where negative air pressure exists on one side of door; contact Berner for additional information. Model MAXAIR has 1/5 HP motors. Both models can be wall mounted or suspended from the ceiling. Maximum recommended mounting height is 8 feet above the floor. Electric heated unit should be installed indoors only and have a minimum clearance of at least 6 feet between the bottom of the unit and the floor and at least 1 inch between the sides and top of the unit and any combustible material. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| L. | Acceptable Products: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Berner Model MAXAIR. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Construction: Provide factory-assembled units of sufficient structural strength to be supported from ends without intermediate support. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Cabinet: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Dimensions: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Not to exceed 7-1/2 inches (191 mm) height by 13-3/4 inches (349 mm) deep. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Finish: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Clear anodized aluminum | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Stainless steel | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Bronze anodized aluminum | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Aluminum with colored baked enamel finish color as selected by the Architect from that manufacturer standard colors. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Riveted construction, with stainless steel rivets. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Motors: direct drive, 1600 rpm, resilient mounted, continuous duty, with internal thermal-overload protection and permanently lubricated sealed sleeve bearings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Fans: Balanced forward curved cross flow, tangential type, flexible hubs mounted in matched fan scrolls. Wheels constructed of aluminum. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | Discharge Nozzle: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Provide uniform velocity across width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Aperture: 2 inches (51 mm) slot by width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Vanes: 7/8 inch (22 mm) minimum high; constructed of airfoil-shaped aluminum extrusions; adjustable plus or minus 20 degrees to deflect airflow. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | Air Intake: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Location: Front. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Screen: Perforated aluminum with extruded aluminum frame. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8. | Heating Elements: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Electric Heating Coil: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | UL approved. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Factory-mounted, factory-wired galvanized steel frame and thermally protected. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Helical coil with point suspension of elements, [single][three] phase. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Thermal cutout: locks out electric heaters when prolonged abnormal over-temperature conditions exist. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Steam/Hot Water Coil: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Certify per ARI 410 | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Construction: 16 gauge galvanized steel casing, 5/8 inches (15.8 mm) outside diameter copper steam/hot water coil with aluminum fins. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Leak-test at 325 psig (2238 kPa) dry nitrogen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Factory mount on air door intake, protected by perforated metal screen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 9. | Controls: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Control Panel: UL listed, pre-wired, with solid-state variable speed control switch. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Switching: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Factory installed Intelliswitch digital programmable controller: Three modes; On-Off-Auto. Time delay off 0 to 10 minutes. Internal thermostat; F or C; off- 50 degree F - 90 degree F. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Automatic Door Switch: Switch automatically activates unit when door opens and deactivates unit when door is closes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Reed Switch: Magnetic. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Remote Control: controller for use with Intelliswitch digital programmable controller. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Sequencing: ___________________________. | |||||||||||||||||||||||||||||||||||||||||||||||||
Star-STF is designed for customer entries up to 6 feet wide with door heights up to 9 feet for environmental separation and up to 8 feet for insect control. Star-STF air doors can resist winds up to 10 MPH and are generally mounted inside building to recirculate warm air which has risen towards ceiling. Star-STN meets requirements of NSF Standard 37 for doors 3 feet and 3-1/2 feet wide with door heights up to 7 feet for insect control. Star-STR is designed for service doors up to 6 feet wide with door heights up to 10 feet for environmental separation and up to 9 feet for insect control. Star-STR can resist winds up to 13 MPH and can be mounted inside or outside the building. Optimum protection is provided when units are mounted on inside of building, flush to the wall and as close to top of door opening as possible. To ensure peak performance keep air stream free of obstructions. Air doors may not be fully effective where negative air pressure exists on one side of door; contact Berner for additional information. Star models are standard with a 3/4 HP motor; an optional 1/2 HP motor is available. Star air doors can be wall mounted or suspended from the ceiling. Maximum recommended mounting height is 8 feet above floor. Electric heated unit should be installed indoors only and require a minimum clearance of 6 feet between the bottom of unit and floor and 4 inches between sides and top of the unit and any combustible material. A minimum of 4 inches is recommended above top for installation and removal of housing. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| M. | Acceptable Products: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Berner Model Star STF. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Berner Model Star STN. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Berner Model Star STR. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Construction: Provide factory assembled units of sufficient structural strength to be supported from ends without intermediate support. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Cabinet: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Dimensions: Not to exceed 14-1/4 inches (362 mm) height by 13 inches (330 mm) deep. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Material: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Corrosion resistant Aluminum with polyester white on white painted finish. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Corrosion resistant Stainless Steel riveted construction, with stainless steel rivets. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Fasteners: Tamper-resistant type. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | Motor: Permanently lubricated and sealed bearings, double extended shafts, continuous duty, with internal thermal-overload protection. | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | 3/4 hp, ball bearings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | 1/2 hp, 3-speed, sleeve bearings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | Fans: Balanced forward curved type, double inlet, mounted in matched fan scrolls with aerodynamically formed air inlet venturies. | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Wheels and housing constructed of galvanized steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8. | Discharge Nozzle: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Provide uniform velocity across width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Aperture: 3-1/2 inches (9 mm) slot by width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Vanes: constructed of airfoil-shaped aluminum extrusions; air-directional vanes adjustable plus or minus 20 degrees to deflect airflow. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 9. | Air Intake: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Location: Front. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Screen: Perforated pattern constructed of the same material used in housing. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 10. | Filters: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Air intake filter re-cleanable aluminum with integral filter clips. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 11. | Heating Elements: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Electric Heating Coil: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | UL approved. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Factory-mounted, in factory-wired control compartment in galvanized steel frame, thermally protected. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Helical coil with point suspension of elements, single or three phase. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Thermal cutout: locks out electric heaters when prolonged abnormal over-temperature conditions exist. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 12. | Controls: | |||||||||||||||||||||||||||||||||||||||||||||||||
Unheated 3/4 hp single speed - standard: switch not included. Unheated 1/2 hp three speed - standard: built-in, on-off, high-med-low switches. Electric heated 3/4 hp single speed - standard: built-in, fan-off-fan/heat switch. Electric 1/2 hp three speed - standard: built-in, fan-off-fan/heat, high-med-low switches. Select options required and delete those not required. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Switching: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Manual Switch: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Factory installed on/off switch. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Remote mount rotary cam hand-off-auto, 1-1/2 hp at 120V/1, 3 hp at 208V/1, 240V/1, or 480V/1. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Wall On/Off Switch and Cover Plate: single phase power only, rated for commercial use max 20 amps, mounted in a wall box. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Unheated Remote Fan Speed Selector Switch: three speed capacity - 1-1/2 hp at 120V/1 and 3 hp at 208V/1, 240V/1 or 480V/1. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Electric Heat Remote Fan Selector Switch: single speed capacity - 1-1/2 hp at 120V/1, 3 hp at 208V/1, 240V/1, or 480V/1. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5) | Electric Heat Remote Fan Speed Selector Switch: three speed capacity - 1-1/2 hp at 120V/1, 3 hp at 208V/1, 240V/1, or 480V/1. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6) | Automatic Door Switch: Switch automatically activates unit when door opens and deactivates unit when door closes. plunger type or roller arm. 120V, 208V, or 240V. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7) | Reed Switch: Magnetic, requires 24V transformer and time delay. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8) | Thermostat: Remote mount thermostat, capacity; 22 amps at 125/277 VAC. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 9) | Time Delay Relay: Adjustable in field from 0.1 second to 10 hour delay. Set delay for 2 minutes unless otherwise indicated. 120V, 208-240V, or 480V. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 10) | Damper plate: mounted on: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | One end of fan housing. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Both ends of fan housing. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Sequencing: ___________________________. | |||||||||||||||||||||||||||||||||||||||||||||||||
At exterior openings, air doors can resist winds up to 8 MPH and are generally mounted inside building to recirculate warm air, which has risen towards ceiling. Air doors may not be fully effective where negative air pressure exists on one side of door; contact Berner for additional information. Models ZEPHYR has a 1/5 HP motor. Both models can be wall mounted or suspended from the ceiling. Maximum recommended mounting height is 8 feet above the floor. Electric heated units should be installed indoors only and have a minimum clearance of at least 6 feet between the bottom of the unit and the floor and at least 1 inch between the sides and top of the unit and any combustible material. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| N. | Acceptable Products: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Berner Model ZEPHYR | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Construction: Provide factory assembled units of sufficient structural strength to be supported from ends without intermediate support. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Cabinet: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Dimensions: Not to exceed: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | 7-1/2 inches (190 mm) height by 13-3/4 inches (349 mm) deep. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Material and Finish: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Clear anodized aluminum. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Bronze. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Stainless steel | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Aluminum with baked enamel finish, color as selected by the Architect from the manufacturers standard colors. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Riveted construction, with stainless steel rivets. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Motors: Direct driven, 1600 rpm, three speed resilient mounted, continuous duty, with internal thermal-overload protection and sealed sleeve bearing permanently lubricated. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Fans: Balanced forward curved cross flow, tangential type, flexible hubs mounted in matched fan scrolls. Wheels constructed of aluminum. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | Discharge Nozzle: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Provide uniform velocity across width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Aperture: 2 inches (51 mm) slot by width of air door. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Vanes: 7/8 inches (22 mm) minimum high; constructed of airfoil-shaped aluminum extrusions; adjustable plus or minus 20 degrees to deflect airflow. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | Air Intake: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Location: Front. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Screen: Perforated aluminum with extruded aluminum frame. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8. | Heating Elements: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Electric Heating Coil: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | UL approved. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Factory-mounted, factory-wired, galvanized steel frame and thermally protected. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Helical coil with point suspension of elements: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a) | Single phase. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b) | Three phase. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Thermal cutout: locks out electric heaters when prolonged abnormal over-temperature conditions exist. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Steam/Hot Water Coil: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Certify per ARI 410 | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Construction: 16 gauge galvanized steel casing, 5/8 inch (15.8 mm) outside diameter copper steam/hot water coil with aluminum fins. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Leak-test at 325 psig (2238 kPa) dry nitrogen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Factory mount on air door intake, protected by perforated metal screen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 9. | Controls: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Control Panel: UL listed, pre-wired, with solid-state variable speed control switch. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Switching: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1) | Factory installed Intelliswitch digital programmable controller: Three modes; On-Off-Auto. Time delay off 0 to 10 minutes. Internal thermostat; F or C; off- 50 degrees F - 90 degrees F. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2) | Automatic Door Switch: Switch automatically activates unit when door opens and deactivates unit when door is closes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3) | Reed Switch: Magnetic. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4) | Remote Control: controller for use with Intelliswitch digital programmable controller. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Sequencing: ___________________________. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2.3 | MOUNTING ACCESSORIES | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Provide brackets and other mounting accessories as required permitting installation and functioning of air door to meet project conditions of use. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Mounting accessories | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Painted, aluminized or galvanized steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Stainless steel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| C. | Mount Type: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Top mounting brackets constructed of steel with white painted enamel finish. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Floor Brackets. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Extension Brackets. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Tandem Brackets. | |||||||||||||||||||||||||||||||||||||||||||||||||
| PART 3 | EXECUTION | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3.1 | EXAMINATION | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Do not begin installation until openings have been properly prepared. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Verify that required utilities are in correct location and are of correct capacities for specified products. | |||||||||||||||||||||||||||||||||||||||||||||||||
| C. | If preparation is the responsibility of another installer, notify Architect of unsatisfactory preparation before proceeding. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3.2 | INSTALLATION | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Install air door/air curtain components in accordance with approved shop drawings and manufacturer's printed installation instructions. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Install air doors plumb, level, and as close as practical to top of opening and face of wall. | |||||||||||||||||||||||||||||||||||||||||||||||||
| C. | Install switches where indicated. | |||||||||||||||||||||||||||||||||||||||||||||||||
| D. | Connection to utilities as specified in Sections of Divisions 15 and 16. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3.3 | 3.3 CLEANING | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Clean prior to startup. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Repair or repaint damage to finishes on exposed-to-view surfaces. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3.4 | PROTECTION | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Protect installed products until completion of project. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Touch-up, repair or replace damaged products before Substantial Completion. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3.5 | FIELD QUALITY CONTROL | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Test and operate air door to be sure that it performs as intended. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Adjust discharge nozzles as required for each opening. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3.6 | SCHEDULE | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Refer to Air Door Schedule appended to this section. | |||||||||||||||||||||||||||||||||||||||||||||||||